Equipment for General Use — Texas Journeyman Exam Study Chapter

Learning Objectives

By the end of this chapter, you will be able to:

4.Identify the scope and general requirements of NEC Article 400 (flexible cords) and Article 402 (fixture wires).
5.Apply the correct ampacity adjustment factors for flexible cords and fixture wires.
6.Distinguish between permitted and prohibited uses of flexible cords.
7.Understand the installation rules for receptacles, including spacing, GFCI, and AFCI requirements.
8.Calculate receptacle loads for general-purpose and multi-outlet assemblies.
9.Apply the correct rules for switches, including snap switches, dimmers, and disconnect requirements.
10.Recognize the special requirements for cord-and-plug-connected appliances and fixed appliances.
11.Navigate the 2026 NEC to locate specific tables and sections quickly under open-book conditions.

1.1 Scope of Article 400 — Flexible Cords and Cables

Article 400 covers the construction, installation, and use of flexible cords and flexible cables. This includes cords like SJOOW, SOOW, and SJT. The NEC does not cover cords that are an integral part of an appliance (e.g., a toaster cord) — those are covered by the appliance standard.

Key definitions to know:

Flexible cord — a conductor assembly with an outer sheath, used for connecting movable equipment.
Cable — a factory assembly of two or more conductors, often with an overall covering.

Ampacity tables: Table 400.5(A)(1) and Table 400.5(A)(2) provide ampacities for flexible cords. These tables are based on not more than three current-carrying conductors. If you have more than three, you must apply the adjustment factors from Table 400.5(B).

Exam trap: Many candidates confuse Table 400.5(A) with Table 310.16 (building wire). They are different. Flexible cord ampacities are generally lower than building wire of the same gauge. Always check which table applies.

Field point: On site, when you extend a cord with a cord cap, the cord must be a listed type and the ampacity must be at least the rating of the equipment. Never use a cord that is smaller than 18 AWG for power, except for certain low-voltage applications.


1.2 Uses and Prohibited Uses of Flexible Cords

Section 400.10 lists permitted uses. The most common are:

Pendants (lighting fixtures suspended by cord)
Wiring of fixtures
Connection of portable lamps, motors, and appliances
Elevator cables
Wiring of cranes and hoists
Connection of stationary equipment to facilitate interchange (e.g., a machine that is occasionally moved)
Prevention of transmission of noise or vibration
Appliances where the cord is part of the listed appliance

Section 400.12 lists prohibited uses. You cannot use flexible cord:

As a substitute for fixed wiring of a structure
Run through holes in walls, ceilings, or floors
Run through doorways, windows, or similar openings
Attached to building surfaces (except with approved methods within 6 ft of the equipment)
Hidden behind walls, ceilings, or floors
Where subject to physical damage

Exam trap: A common question asks whether a cord can be run through a wall to connect a window AC unit. The answer is no — that is a prohibited use. The cord must be visible and accessible.

Field point: When you install a cord for a hardwired appliance that must be moved for service, keep the cord length short and use a strain relief. Never staple cords to the wall.


1.3 Fixture Wires — Article 402

Fixture wires are used for internal wiring of luminaires and for connecting luminaires to branch circuits. They are smaller than standard branch-circuit conductors and are covered in Article 402.

Key points:

Fixture wire types are listed in Table 402.3 (e.g., TFFN, THHN, XHHW).
Ampacities are found in Table 402.5.
Fixture wires must be at least 18 AWG for general use, but 20 AWG is allowed for special applications (e.g., control circuits) if the voltage does not exceed 300 V.

Exam trap: You cannot use fixture wire as a branch-circuit conductor. Branch circuits require conductors rated at least 14 AWG for 15 A circuits (unless a specific exception applies).

Field point: When wiring a lay-in troffer, you will often use fixture whips (pre-wired flexible metal conduit with fixture wires). These are acceptable because they are part of a listed assembly.


1.4 Receptacle Installation — Article 406

Article 406 covers receptacles, cord connectors, and attachment plugs. Key sections:

406.4 — Installation requirements. Receptacles must be grounded, polarized, and secured.
406.5 — Receptacle mounting. Faceplates must fit tightly. Receptacles in wet or damp locations must be weatherproof.
406.6 — Receptacles must not be installed in a back-to-back position in the same stud space unless they are separated by a fire-resistant barrier.

Receptacle spacing (210.52): In dwelling units, receptacles must be installed so that no point along the floor line is more than 6 ft from a receptacle. This is the 6-ft rule. The logic: a lamp cord is typically 6 ft long, so you can place a lamp anywhere and reach a receptacle.

Exam trap: The 6-ft rule applies to wall space — not to the center of the room. Also, doorways, fireplaces, and fixed cabinets do not count as wall space.

GFCI requirements (210.8): In dwelling units, GFCI protection is required for receptacles in:

Bathrooms
Garages (including unfinished basements)
Outdoors
Crawl spaces
Kitchens (countertop and within 6 ft of sink)
Laundry areas
Boathouses

AFCI requirements (210.12): AFCI protection is required for branch circuits supplying outlets in dwelling unit bedrooms, living rooms, hallways, and similar areas. The 2026 NEC continues to expand AFCI coverage to more areas.

Field point: When you rough-in a kitchen, you must place countertop receptacles so that no point along the counter is more than 2 ft from a receptacle (measured horizontally). This is the 2-ft rule for countertops.


1.5 Receptacle Load Calculations — Article 220

For general-purpose receptacles in non-dwelling occupancies, the NEC requires a load of 180 VA per receptacle (220.14(I)). This is a unit load — you count the number of receptacles and multiply by 180 VA.

Multi-outlet assemblies (220.14(H)): For a continuous run of receptacles (e.g., a plugmold strip), the load is:

180 VA per 5 ft of run, if the run is not likely to have many appliances plugged in simultaneously.
180 VA per 1 ft of run, if the run is likely to be used simultaneously (e.g., a workbench in a shop).

Exam trap: For dwelling units, you do not apply the 180 VA rule to general-purpose receptacles. Dwelling unit general loads are calculated using the VA per square foot method (3 VA per sq ft for general lighting and receptacles combined).

Field point: When you calculate a commercial office, count every duplex receptacle as 180 VA. A duplex counts as one receptacle for load purposes, not two.


1.6 Switches — Article 404

Article 404 covers switches, including snap switches, dimmers, and control devices.

Key requirements:

404.4 — Switches must not disconnect the grounded conductor unless the switch simultaneously disconnects all ungrounded conductors.
404.6 — The switching of a circuit must be on the ungrounded (hot) conductor.
404.9 — Snap switches must be enclosed in a listed box or a noncombustible housing.

Ratings: A general-use snap switch must be rated for the voltage and current of the circuit. If the switch controls a motor load, the switch must have a horsepower rating.

Dimmers (404.14(E)): Dimmers must be rated for the type of load (incandescent, LED, fluorescent). If you use a dimmer on an LED load, the dimmer must be listed for LED loads. Standard incandescent dimmers will cause flicker and possible damage.

Exam trap: A common question asks whether a switch can be used to control a 20 A circuit. The answer is yes, if the switch is rated 20 A. A 15 A switch cannot control a 20 A circuit unless the load is 15 A or less and the switch is marked "15 A."

Field point: When you install a three-way switch, the common terminal is usually darker in color. Always verify the wiring diagram on the switch — do not rely on color alone.


1.7 Cord-and-Plug-Connected and Fixed Appliances — Article 422

Article 422 covers appliances, including fixed, stationary, and portable types.

Key requirements:

422.10 — The branch-circuit rating must not be less than the appliance rating.
422.12 — Central heating equipment must be on a separate branch circuit.
422.16 — Flexible cords for appliances must be a listed type and must be installed so that they are not subject to strain.

Disconnecting means (422.31): For fixed appliances, a disconnecting means must be provided. This can be a switch, a circuit breaker, or a cord-and-plug connection (if the plug is accessible).

Exam trap: A range or oven that is hardwired must have a disconnecting means within sight or be capable of being locked in the open position. A cord-and-plug range with a accessible plug is acceptable.

Field point: When you install a garbage disposal, you must provide a disconnecting means. A cord-and-plug connection under the sink is common, but the receptacle must be GFCI-protected if within 6 ft of the sink.


1.8 Fixed Electric Space Heating — Article 424

Article 424 covers fixed electric space heating equipment, including baseboard heaters, wall heaters, and radiant heating cables.

Key requirements:

424.3 — All space heating equipment must be marked with the manufacturer's name, voltage, wattage, and phase.
424.19 — Disconnecting means must be provided for each heater. This can be a switch, a circuit breaker, or a cord-and-plug connection.
424.22 — Resistance-type heating elements must have overcurrent protection not exceeding 60 A.

Exam trap: For baseboard heaters, the total load is calculated at 100% of the nameplate rating. You cannot use the general lighting load calculation for heaters.

Field point: When you wire a baseboard heater, the thermostat must be rated for the full current of the heater. Many thermostats are rated for 16 A or 22 A — check the label.


1.9 Code Navigation — Where to Find It

Use this quick-reference table during the exam:

ConceptNEC Location
Flexible cord ampacityTable 400.5(A)(1), 400.5(A)(2)
Flexible cord adjustment factorsTable 400.5(B)
Permitted uses of flexible cords400.10
Prohibited uses of flexible cords400.12
Fixture wire typesTable 402.3
Fixture wire ampacityTable 402.5
Receptacle installationArticle 406
Receptacle spacing (dwelling)210.52
GFCI requirements210.8
AFCI requirements210.12
Receptacle load (non-dwelling)220.14(I)
Multi-outlet assembly load220.14(H)
Switch requirementsArticle 404
Appliance requirementsArticle 422
Space heating requirementsArticle 424

1.10 Common Exam Traps — Final Review

112.Cord ampacity vs. wire ampacity: Always use Table 400.5 for cords, not Table 310.16.
113.6-ft rule vs. 2-ft rule: The 6-ft rule is for wall space; the 2-ft rule is for countertops.
114.180 VA per receptacle: Applies to non-dwelling only. Dwelling units use square footage.
115.Switching the grounded conductor: Never allowed unless all ungrounded conductors are switched simultaneously.
116.Dimmer ratings: Must match the load type (LED, incandescent, etc.).
117.Disconnecting means: Always required for fixed appliances and heaters — know the exceptions.
118.Fixture wires are not branch circuits: 18 AWG fixture wire is not a substitute for 14 AWG branch circuit wire.

1.11 Practical Field Summary

As a journeyman, you will apply these rules daily:

When pulling flexible cords, always use a listed cord grip or strain relief at the box.
For receptacle spacing, measure along the wall line, not diagonally across the room.
In kitchens, remember that all countertop receptacles must be GFCI-protected, and the 2-ft rule applies to the countertop length.
When installing a dimmer, verify the minimum and maximum load ratings — many dimmers require a minimum load to operate correctly.
For baseboard heaters, always install the thermostat on the wall, not on the heater itself, unless the heater is listed for a built-in thermostat.

End of Chapter — Equipment for General Use.