Motors, Transformers & Overcurrent Protection
JourneymanPractice study guide with diagrams.
Motors, Transformers & Overcurrent Protection
Learning Objectives
By the end of this chapter, you should be able to:
1.1 The Scope of Articles 430 and 450
The NEC treats motors and transformers as distinct equipment with unique protection requirements. Article 430 governs all motor circuits and controllers, while Article 450 governs transformers and transformer vaults. Overcurrent protection is covered generally in Article 240, but specific applications for motors and transformers override these general rules.
A critical distinction: a motor has two separate protection needs. Overload protection (thermal) protects the motor from sustained overcurrent due to mechanical overload or stalled rotor. Short-circuit and ground-fault protection protects the conductors and equipment from high-level fault currents. These are not interchangeable. Overload devices are sized based on the motor's nameplate full-load current (FLC), while short-circuit devices are sized based on the motor's FLC from the NEC tables, not the nameplate.
1.2 Motor Full-Load Current: Tables vs. Nameplate
For all calculations involving motor branch circuits, feeders, and short-circuit protection, you must use the NEC Tables 430.247 through 430.250 to determine the motor's full-load current. These tables list FLC values for DC motors (Table 430.247), single-phase AC motors (Table 430.248), and three-phase AC motors (Tables 430.250). The nameplate current is used only for sizing overload relays and for adjusting the motor's actual thermal protection.
Exam Trap: A question will give you a motor nameplate current of 18 A, but the table value for that horsepower and voltage is 22 A. You must use 22 A for conductor sizing and short-circuit protection. Using the nameplate value will result in an undersized circuit.
1.3 Motor Branch-Circuit Conductors (430.22)
Branch-circuit conductors supplying a single motor must have an ampacity of not less than 125% of the motor's FLC as determined from the tables. This 125% factor accounts for the continuous nature of the motor load.
Example: A 10 HP, 208 V, three-phase motor has a table FLC of 30.8 A. The minimum conductor ampacity is 30.8 A × 1.25 = 38.5 A. You would select a conductor with an ampacity of at least 38.5 A, typically a #8 AWG copper at 75°C (rated 50 A).
For motors with a service factor of 1.15 or greater, or a temperature rise of 40°C or less, the conductors are still sized at 125% of the table FLC. The higher service factor only affects overload protection, not conductor sizing.
1.4 Motor Overload Protection (430.32)
Overload devices must protect the motor, motor control apparatus, and motor branch-circuit conductors against excessive heating. The primary rule is that the overload device must be sized at not more than 115% of the motor nameplate current for motors with a service factor of 1.15 or more, or a temperature rise of 40°C or less. For all other motors, the limit is 125% of the nameplate current.
If the chosen overload size is insufficient to start the motor (e.g., it trips during acceleration), the NEC permits a higher rating, but it cannot exceed 140% of the nameplate current for motors with a service factor of 1.15 or higher, or 130% for others. This is a common source of confusion; the initial sizing is 115%/125%, and the maximum permitted is 140%/130%.
Field Point: A journeyman will typically set overload relays based on the motor nameplate, but must verify the service factor. If a motor has a service factor of 1.0, the overloads are set at 115% of nameplate, not 125%.
1.5 Short-Circuit and Ground-Fault Protection (430.52)
This is the most calculation-heavy section for motors. The branch-circuit short-circuit and ground-fault protective device (typically a fuse or circuit breaker) must be sized based on a percentage of the motor's table FLC. The percentages vary by device type:
If the calculated value does not correspond to a standard fuse or breaker size (Table 240.6(A)), you may round up to the next standard size, but only if the motor can start without nuisance tripping. However, there is a hard cap: the maximum permitted size is 400% of FLC for non-time-delay fuses and instantaneous-trip breakers, and 225% of FLC for time-delay fuses and inverse-time breakers.
Exam Trap: A question will ask for the maximum permitted fuse size. You must first calculate the standard percentage (e.g., 175% of FLC), then round up to the next standard size, but you cannot exceed the 225% cap. If 175% of FLC is 40 A, you can use a 45 A fuse (next standard size). But if 175% of FLC is 60 A, you cannot use a 70 A fuse if the cap is 225% of FLC (which is 77 A) — you can, but you must check the cap. The cap is the absolute maximum.
1.6 Motor Feeder Conductors and Protection (430.24, 430.62)
A feeder supplying two or more motors must have an ampacity of not less than 125% of the largest motor FLC plus the sum of the FLCs of all other motors on that feeder. This is a simple addition problem, but the largest motor must be identified correctly.
The feeder short-circuit and ground-fault protective device is sized based on the largest branch-circuit protective device permitted for the largest motor, plus the sum of the FLCs of the other motors. This is a two-step process: first, calculate the maximum branch-circuit device for the largest motor (using the percentages in 430.52), then add the FLCs of all other motors.
Example: Feeder supplies Motor A (FLC 20 A) and Motor B (FLC 15 A). Motor A uses a time-delay fuse at 175% = 35 A (next standard size 35 A). Motor B uses a time-delay fuse at 175% = 26.25 A (next standard size 30 A). The feeder fuse is 35 A + 15 A = 50 A.
1.7 Transformer Overcurrent Protection (450.3)
Transformer protection is simpler than motor protection, but has its own traps. The primary rule is that transformers must be protected on the primary side only, unless specific conditions require secondary protection. The size of the primary overcurrent device depends on whether the transformer has primary and secondary protection or primary-only protection.
For a transformer with primary-only protection, the primary device must be sized at not more than 125% of the rated primary current for transformers over 600 V, and not more than 125% for transformers 600 V or less. If 125% does not correspond to a standard size, you may round up to the next standard size, but the maximum is 250% for primary-only protection.
For a transformer with both primary and secondary protection, the primary device can be sized at not more than 250% of the rated primary current, and the secondary device at not more than 125% of the rated secondary current. This is the most common configuration in commercial work.
Calculation: To find the transformer current, use the formula: I = (kVA × 1000) / (E × 1.732) for three-phase, or I = (kVA × 1000) / E for single-phase. You must know the transformer voltage and kVA rating.
Example: A 75 kVA, 480 V three-phase transformer has a primary current of (75 × 1000) / (480 × 1.732) = 90.2 A. With primary and secondary protection, the primary device can be 250% of 90.2 A = 225.5 A. You would select a 225 A fuse or breaker (standard size). The secondary protection would be based on the secondary voltage.
1.8 Standard Ampere Ratings (Table 240.6(A))
All overcurrent protection devices must be sized to standard ratings unless otherwise permitted. The standard ratings include: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 A. You must memorize the common ones (15 through 800) for the exam.
Exam Trap: When rounding up, you may only round to the next standard size, not an arbitrary value. If your calculated value is 42 A, you can use a 45 A device, not a 50 A device unless the 45 A is not standard (it is).
1.9 Code Navigation: Where to Look
1.10 Practical Field Points
1.11 Common Exam Traps
1.12 Summary of Key Formulas
1.13 Final Exam Strategy
When you encounter a motor or transformer calculation on the exam, follow this sequence:
Do not skip the cap check. Many questions are designed to see if you know the absolute maximum, not just the standard calculation. If your calculated value exceeds the cap, you must use the cap value, not the calculated value.
Finally, remember that the NEC is a minimum standard. In the field, you may choose to install larger conductors or smaller breakers for operational reasons, but you must never go below the minimums calculated here. The exam will always test the minimum requirements.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free