NEC 240 — Overcurrent Protection (Washington)
Journeyman Practice study guide with diagrams.
NEC 240 — Overcurrent Protection (Washington Journeyman)
Learning Objectives
1.1 Scope and Recognized OCPDs (240.1, 240.7)
Article 240 Parts I through VII give the general requirements for overcurrent protection and OCPDs not over 1000 volts ac, 1500 volts dc, nominal; Part VIII covers supervised industrial installations at those limits (240.1). Section 240.2 requires listing of OCPDs, relays and circuit breakers providing GFPE, ground-fault circuit interrupters, and fuse reducers. Section 240.3 permits reconditioning of low-voltage power circuit breakers, electromechanical protective relays, and current transformers, but bars it for GFPE equipment, GFCIs, low-voltage fuseholders and nonrenewable fuses, molded-case circuit breakers, and power circuit breaker electronic trip units.
Section 240.7 lists the permitted OCPDs: molded-case, low-voltage power, and solid-state breakers; Class C through Class T fuses; Edison-base, Type C, or Type S fuses; and other fuses or breakers labeled as suitable. Part I also bars thermal relays from short-circuit or ground-fault protection (240.9), requires an OCPD in series with each ungrounded conductor (240.15), sets a minimum interrupting rating of 5000 amperes (240.16), and bars an OCPD in series with an intentionally grounded conductor (240.22).
1.2 Protection of Conductors and the Next-Size-Up Rule (240.4)
Conductors other than flexible cords, flexible cables, and fixture wires must be protected in accordance with their ampacities in 310.14 unless otherwise permitted or required in 240.4(A) through 240.4(H).
(B) OCPDs rated 800 amperes or less. The next higher standard rating above the conductor ampacity is permitted only where: the conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads; the ampacity does not correspond with the standard ampere rating of a fuse or a circuit breaker without overload trip adjustments above its rating; and the next higher standard rating does not exceed 800 amperes. An adjustable trip device so installed may be set to the next higher standard value in Table 240.6(A) where restricted access per 240.6(C) applies. An ampacity of 185 amperes takes 200 amperes; 225 amperes is two steps up and 175 amperes is below the ampacity.
(C) Where the OCPD is rated over 800 amperes, the conductor ampacity must be equal to or greater than the rating of the OCPD defined in 240.6.
(D) Small conductors. Unless permitted in 240.4(E) or 240.4(G), overcurrent protection may not exceed the following after correction factors for ambient temperature and number of conductors are applied:
| Conductor | Maximum overcurrent protection |
|---|---|
| 18 AWG copper | 7 amperes (continuous loads not over 5.6 amperes; listed OCPD or a Class CC, CF, J, or T fuse) |
| 16 AWG copper | 10 amperes (continuous loads not over 8 amperes; same marking or fuse types) |
| 14 AWG copper-clad aluminum | 10 amperes (continuous loads not over 8 amperes) |
| 14 AWG copper | 15 amperes |
| 12 AWG aluminum and copper-clad aluminum | 15 amperes |
| 12 AWG copper | 20 amperes |
| 10 AWG aluminum and copper-clad aluminum | 25 amperes |
| 10 AWG copper | 30 amperes |
(E) Taps may be protected per 210.19(C), 210.19(D), 240.5(B)(2), 240.21, 368.17(B), 368.17(C), and 430.53(D).
(F) Single-phase (other than 2-wire) and multiphase (other than delta-delta, 3-wire) transformer secondary conductors are not protected by the primary OCPD; a 2-wire single-phase or 3-wire delta-delta secondary may be protected on the primary side per 450.5, where that protection does not exceed the secondary ampacity multiplied by the secondary-to-primary voltage ratio.
(G) Table 240.4(G) lists conductors whose overcurrent protection is provided elsewhere — air-conditioning and refrigeration, capacitors, Type ITC control and instrumentation, welders, fire alarm, motor-operated appliances, motors and motor controls, phase converters, remote-control and power-limited circuits, and secondary ties — the applications where the limits of 240.4(D) do not apply.
(H) Dwelling unit service and feeder conductors may be protected at the ampacity values of 310.12, which covers one-family dwellings and the individual units of two-family and multifamily dwellings on single-phase, 120/240-volt systems and two-ungrounded-conductor-plus-neutral feeders from a 208Y/120 volt system; a service rated 100 amperes through 400 amperes may be sized by those values.
1.3 Standard Ampere Ratings and Adjustable Trip Settings (240.6)
Table 240.6(A) gives the standard ampere ratings for fuses and inverse time circuit breakers: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 amperes. Additional standard ratings for fuses are 1, 3, 6, and 601 amperes, and nonstandard ratings are permitted for use. Values not listed, such as 230, 260, 275, 310, 325, 550, 650, 780, 1100, 1300, 1400, and 1500, are not standard, so a rating above 1000 amperes lands on 1200, 1600, 2000, 2500, 3000, 4000, 5000, or 6000 amperes.
Section 240.6(B) rates an adjustable-trip breaker with external means for adjusting the current setting (long-time pickup setting) at the maximum setting possible unless 240.6(C) or 240.6(D) applies. Section 240.6(C) permits the adjusted setting where the breaker cannot be adjusted remotely and restricted access is achieved by removable and sealable covers, bolted doors, locked doors accessible only to qualified personnel, or password protection. Section 240.6(D) permits the adjusted setting for a remotely adjustable breaker only where that local restricted access exists and remote access is through a local nonnetworked interface or a networked interface meeting the cybersecurity conditions of 240.6(D). Otherwise the rating is the highest possible setting.
1.4 Ground-Fault Protection of Equipment (240.13 and 230.95)
GFPE protects equipment from damaging line-to-ground fault currents; it is not the 5-milliampere personnel protection of a Class A ground-fault circuit interrupter. Section 240.13(A) requires GFPE, provided in accordance with 230.95, for solidly grounded wye systems of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase at each individual device used as a building or structure main disconnecting means rated 1000 amperes or more; 240.13(B) requires it for solidly grounded dc systems of more than 150 volts to ground but not exceeding 1500 volts dc line-to-line at a main disconnecting means rated 1000 amperes or more. Both exclude the disconnecting means for continuous industrial processes where a nonorderly shutdown would introduce additional hazards, installations where ground-fault protection is provided by other requirements, and fire pumps.
Section 230.95 applies the same requirement to services: GFPE for solidly grounded wye services of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase at each service disconnect rated 1000 amperes or more (230.95(A)), and for solidly grounded dc services of more than 150 volts to ground but not exceeding 1500 volts dc line-to-line (230.95(B)). "1000 amperes or more" includes exactly 1000 amperes, so a 120/240-volt single-phase service and a 600-ampere disconnect are outside the rule.
The grounded conductor must be connected directly to ground through a grounding electrode system, as specified in 250.50, without inserting any resistor or impedance device; a grounding resistor that limits fault current defeats the low-impedance path the section requires, and connection through the service enclosure alone omits the electrode system. Section 250.50 builds that system from all grounding electrodes described in 250.52(A)(1) through 250.52(A)(7) present at each building or structure served. Where GFPE is installed it must be performance tested as a system considering all sources (230.95(C)).
1.5 Location in Circuit: Feeder Taps (240.21(B))
Overcurrent protection is provided in each ungrounded circuit conductor at the point where the conductors receive their supply, except as specified in 240.21(A) through 240.21(H), and conductors supplied under 240.21(B) through 240.21(H) may not supply another conductor except through an OCPD meeting 240.4. For taps the next-size-up rule is unavailable: Section 240.4(B) shall not be permitted for tap conductors.
1.6 Transformer Secondary Conductors (240.21(C))
A set of conductors feeding a single load, or each set feeding separate loads, may connect to a transformer secondary without overcurrent protection at the secondary as specified in 240.21(C)(1) through 240.21(C)(6). Section 240.4(B) shall not be permitted for transformer secondary conductors.
The arithmetic is the exam favorite. With a 400-ampere primary OCPD on a transformer rated 480 volts to 208/120 volts, the one-third term is _133.3 A_ and the voltage-ratio term is 400 multiplied by 208/480, or _173.3 A_. The larger governs, so the secondary conductors must carry at least _173.3 A_, and the termination must be a standard rating at or above that value. Those decimals are products of the rules, not code text and not NEC sections.
1.7 Series Ratings and OCPD Location (240.86 and 240.24)
Where a breaker is used on a circuit whose available fault current exceeds its marked interrupting rating by connecting it on the load side of an approved OCPD with a higher rating, the breaker must meet 240.86(A), 240.86(B), and 240.86(C). A combination selected under engineering supervision in existing installations must be selected by a licensed professional engineer engaged primarily in the design or maintenance of electrical installations, documented and stamped, and field marked on the end-use equipment with the series combination rating including identification of the upstream device. Engineered combinations are marked per 110.22(B). Field-marking a breaker with a higher interrupting rating, or paralleling it with the upstream device, is not a series-rating method.
Section 240.24 requires breakers and switches containing fuses to be readily accessible with the center of the grip of the operating handle in its highest position not more than 2.0 m (6 ft 7 in.) above the grade, floor, or working platform, unless the location is a busway per 368.17(C), supplementary protection per 240.10, an OCPD per 225.40 or 230.92, or (240.24(A)(4)) an OCPD adjacent to the utilization equipment it supplies, where access by portable means is permitted. Service and feeder OCPDs supplying more than one occupancy may be management-only where building management provides electric service and maintenance under continuous supervision in multiple-occupancy buildings and guest rooms or guest suites (240.24(B)(1)); branch-circuit OCPDs for guest rooms, guest suites, or sleeping rooms in dormitory units without permanent cooking provisions may be similarly restricted (240.24(B)(2)). OCPDs must not be exposed to physical damage (240.24(C)), in the vicinity of easily ignitible material such as clothes closets (240.24(D)), in bathrooms, showering facilities, or locker rooms with showering facilities other than supplementary protection (240.24(E)), or over the steps of a stairway (240.24(F)).
Elsewhere in the article, 240.50 through 240.54 limit plug fuses to circuits not exceeding 125 volts between conductors and 150 volts line-to-neutral, and 240.87 requires arc energy reduction where the highest continuous current trip setting of a breaker is 1200 amperes or higher.
1.8 Flexible Cords, Fixture Wire, and Supervised Industrial Installations (240.5, 240.91)
Flexible cord and flexible cable, must be protected in accordance with their ampacity as specified in Table 400.5(A)(1) and Table 400.5(A)(2), and fixture wire in accordance with Table 402.5; supplementary protection per 240.10 is permitted as an acceptable means (240.5(A)). Under 240.5(B), cord supplied by a branch circuit is protected by 240.5(B)(1) (supply cord of a listed appliance or luminaire), 240.5(B)(3) (listed extension cord sets), or 240.5(B)(4) (field assembled extension cord sets on a 20-ampere circuit with 16 AWG and larger); fixture wire is protected by 240.5(B)(2), permitting 18 AWG up to 15 m (50 ft), 16 AWG up to 30 m (100 ft), and 14 AWG and larger on 20-ampere circuits. For supervised industrial installations used exclusively for manufacturing or process control activities (240.90), 240.91(B) permits conductor ampacity at 95 percent of the rating of an OCPD rated over 800 amperes.
1.9 Code Navigation
| Topic | NEC Section | What it covers |
|---|---|---|
| Recognized devices | 240.7 | Permitted breakers and fuses; molded-case, low-voltage power, solid-state, Class C through Class T, Edison-base, Type S |
| Next-size-up and over 800 amperes | 240.4(B), 240.4(C) | Next higher standard rating capped at 800 amperes; ampacity at least the rating above 800 amperes |
| Small conductors and specific applications | 240.4(D), 240.4(G), Table 240.4(G) | Limits from 18 AWG copper through 10 AWG copper, and the applications where they do not apply |
| Standard ratings and trip settings | 240.6, Table 240.6(A) | Standard ratings; additional fuse ratings of 1, 3, 6, and 601 amperes; adjustable-trip rules of 240.6(B) through 240.6(D) |
| Ground-fault protection of equipment | 240.13, 230.95, 250.50 | GFPE for grounded wye and dc systems; direct connection of the grounded conductor through the electrode system |
| Feeder taps and transformer secondary conductors | 240.21(B), 240.21(C) | 10 ft, 25 ft, transformer, high bay, outside, industrial, and primary-protection rules |
| Accessibility and location | 240.24 | Readily accessible, the 2.0 m (6 ft 7 in.) handle height, portable access, closets, bathrooms, stairways |
Common Exam Traps
Practical Field Points
Summary
Article 240 answers two questions: what protects the conductor, and where the protective device may be installed. Section 240.4 states the general rule that conductors are protected in accordance with their ampacities in 310.14, with its exceptions in 240.4(A) through 240.4(H) — among them the next-size-up rule capped at 800 amperes (240.4(B)), the requirement that ampacity be at least the OCPD rating above 800 amperes (240.4(C)), the small-conductor limits from 18 AWG copper through 10 AWG copper (240.4(D)), the tap and transformer permissions of 240.4(E) and 240.4(F), the applications of Table 240.4(G), and the dwelling ampacities of 310.12 reached through 240.4(H). Ratings come from Table 240.6(A), with 1, 3, 6, and 601 amperes added for fuses, and an adjustable-trip breaker is rated at the maximum setting possible unless the restricted access of 240.6(C) applies. Ground-fault protection of equipment is required for solidly grounded wye systems over 150 volts to ground and not over 1000 volts phase-to-phase at a main or service disconnect rated 1000 amperes or more, with the grounded conductor connected directly to ground through a grounding electrode system as specified in 250.50 and no resistor or impedance device inserted. The location rules of 240.21 drive the field work — the 10 ft, 25 ft, transformer, high bay, and outside tap rules of 240.21(B) and the transformer secondary rules of 240.21(C), with 240.4(B) prohibited in both — while 240.86 limits series-rated systems to documented engineered or tested combinations marked as 110.22 requires, and 240.24 keeps OCPDs readily accessible and out of bathrooms, closets, and stairway steps.