Wiring & Protection
JourneymanPractice study guide with diagrams.
Wiring & Protection
Learning Objectives
By the end of this chapter, you should be able to:
1.1 Scope and Structure of Chapter 2
Article 200 through 285 of the NEC comprise Chapter 2, titled "Wiring and Protection." This chapter is the backbone of any electrical installation because it governs the safety envelope of the system: how electricity is grounded, how conductors are sized, and how they are protected from overcurrent.
The chapter is organized into logical groups:
Exam Trap: Many candidates confuse Article 210 (branch circuits) with Article 215 (feeders). Remember: a branch circuit is the wiring between the final overcurrent device and the outlet(s). A feeder is the wiring between the service equipment and the branch-circuit OCPD.
1.2 Branch Circuits (Article 210)
A branch circuit is defined as the conductors between the final overcurrent device protecting the circuit and the outlet(s). The NEC sets minimum ratings for branch circuits based on the connected load.
1.2.1 General Requirements (210.19, 210.20)
Field Point: When installing a 20 A circuit for a continuous load like a heater, you must use a conductor rated for at least 25 A (20 A × 1.25). That means 12 AWG copper (rated 20 A at 60 °C) is not sufficient; you would need 10 AWG or a conductor with a higher temperature rating if terminations permit.
1.2.2 Required Outlets (210.52)
For dwelling units, the NEC mandates specific outlet locations:
1.3 Feeders (Article 215)
Feeders carry power from the service equipment or a downstream panelboard to a branch-circuit panelboard or a specific load. The minimum feeder ampacity is the sum of the noncontinuous loads plus 125% of the continuous loads supplied by the feeder.
Exam Trap: The 125% factor for continuous loads applies to both the conductor ampacity and the OCPD rating. Do not apply it twice to the same load.
1.4 Services (Article 230)
Service conductors connect the utility supply to the service disconnecting means. Key requirements:
Field Point: The service entrance conductor ampacity is based on the calculated load, not the sum of the branch-circuit OCPDs. A 200 A service does not require 200 A of conductor if the calculated load is only 150 A, but in practice, most AHJs require the conductor to match the service rating.
1.5 Load Calculations (Article 220)
Load calculations determine the minimum service or feeder size. The NEC provides two methods: the standard method (220.40 through 220.61) and the optional method (220.82 through 220.85) for dwelling units and certain other occupancies.
1.5.1 Standard Method – Dwelling Unit (220.42, 220.52)
1.5.2 Optional Method – Dwelling Unit (220.82)
This method is simpler and often yields a smaller service. It uses the total connected load (all loads at 100%) and applies a single demand factor based on the first 10 kVA at 100%, the next 10 kVA at 40%, and the remainder at 30%.
Exam Trap: The optional method is only permitted for dwelling units with a total connected load served by a single 3-wire, 120/240 V or similar system. It cannot be used for commercial or industrial occupancies.
1.6 Overcurrent Protection (Article 240)
Overcurrent protection devices (fuses and circuit breakers) protect conductors and equipment from excessive current. The OCPD must:
1.6.1 The "Next Size Up" Rule (240.4(B))
If the conductor ampacity does not correspond to a standard OCPD rating (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000 A), you may use the next higher standard size, provided:
Example: A 10 AWG copper conductor rated 35 A at 75 °C can be protected by a 40 A breaker, because 35 A is not a standard size and 40 A is the next standard size up.
Field Point: This rule does not apply to branch circuits supplying receptacles. A 15 A receptacle circuit must use a 15 A breaker, even if the wire is 12 AWG.
1.7 Grounding and Bonding (Article 250)
Article 250 is the most heavily tested article in the NEC. The core concepts are:
1.7.1 System Grounding (250.20, 250.24)
1.7.2 Equipment Grounding Conductors (EGC) (250.118, 250.122)
1.7.3 Bonding Jumpers (250.102)
Exam Trap: The grounded conductor (neutral) is not permitted to be used as an EGC on the load side of the service disconnecting means. This is a common violation and a frequent exam question.
1.8 Conductor Ampacity and Tables
Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. The NEC provides ampacity tables in Article 310 (specifically Table 310.16 for copper and aluminum at 60 °C, 75 °C, and 90 °C).
1.8.1 Table 310.16 – Key Rows
Critical Rule: The ampacity of a conductor is limited by the lowest temperature rating of any termination, device, or conductor in the circuit. Most standard breakers and lugs are rated 60 °C or 75 °C. Therefore, you cannot use the 90 °C column for ampacity unless all terminations are rated 90 °C (rare).
1.8.2 Correction and Adjustment Factors
Exam Trap: Apply the adjustment factor first, then the correction factor, to the base ampacity from Table 310.16. Do not combine them into a single percentage.
1.9 Voltage Drop (Informational Only)
The NEC does not mandate a specific voltage drop percentage, but Informational Note No. 2 to 210.19(A) recommends limiting voltage drop to 3% for branch circuits and 5% for feeders plus branch circuits (total). Many local jurisdictions adopt these as enforceable limits.
Field Point: For long runs, calculate voltage drop using the formula: VD = (2 × K × I × L) / CM, where K is the conductor resistivity (12.9 for copper, 21.2 for aluminum), I is the current, L is the one-way length in feet, and CM is the circular mil area of the conductor.
1.10 Code Navigation: Where to Find It
| Concept | NEC Location |
|---|---|
| Branch circuit definitions and requirements | Article 210, Sections 210.1–210.52 |
| Feeder requirements | Article 215, Sections 215.1–215.3 |
| Load calculations (standard) | Article 220, Sections 220.40–220.61 |
| Load calculations (optional) | Article 220, Sections 220.82–220.85 |
| Service entrance requirements | Article 230, Sections 230.1–230.95 |
| Overcurrent protection devices | Article 240, Sections 240.1–240.100 |
| Grounding and bonding | Article 250, Sections 250.1–250.122 |
| Grounding electrode conductor sizing | Table 250.66 |
| Equipment grounding conductor sizing | Table 250.122 |
| Conductor ampacity tables | Table 310.16 |
| Ambient temperature correction | Table 310.15(B)(1) |
| Adjustment factors (bundling) | Table 310.15(C)(1) |
| Standard OCPD ratings | Section 240.6(A) |
1.11 Common Exam Traps and Field Errors
1.12 Practical Field Application
On the job, a journeyman electrician uses Chapter 2 every day:
Final Tip: In the open-book exam, do not memorize every table. Instead, memorize the structure of Chapter 2 and the location of each table. When you see a question about grounding electrode conductor size, your hand should go immediately to Table 250.66. When you see a question about equipment grounding, your hand goes to Table 250.122. Speed and accuracy in code navigation are your greatest assets.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free