Chapter I

Circuit Calculations (Ohm's Law)

JourneymanPractice study guide with diagrams.

Circuit Calculations (Ohm's Law)

Learning Objectives

By the end of this chapter, you should be able to:

4.Apply Ohm's Law and the power formula to solve for voltage, current, resistance, and power in DC and AC (resistive) circuits.
5.Calculate equivalent resistance, current, and voltage drops for series, parallel, and series-parallel circuits.
6.Perform voltage drop calculations in accordance with NEC 210.19(A)(1) and associated Informational Notes.
7.Distinguish between conductor ampacity and circuit load calculations, and know which NEC Article governs each.
8.Identify the correct Massachusetts amendments (527 CMR 12.00) that affect circuit sizing and overcurrent protection.
9.Recognize common exam traps involving unit conversions, rounding, and misapplication of formulas.

1.1 Fundamental Units and Definitions

Before any calculation, you must be fluent in the base units:

Volt (V) – Electromotive force or potential difference.
Ampere (A) – Rate of electron flow (current).
Ohm (Ω) – Opposition to current flow (resistance).
Watt (W) – Rate of doing work (real power).
Volt-ampere (VA) – Apparent power in AC circuits; for purely resistive loads, VA = W.

Key relationships to memorize:

Ohm's Law: V = I × R
Power Formula: P = V × I
Derived: P = I² × R and P = V² / R

For AC circuits with reactance (motors, transformers), you must distinguish between:

Real Power (W) = V × I × power factor (pf)
Apparent Power (VA) = V × I
Reactive Power (VAR) = V × I × sin(θ)

For the Massachusetts Journeyman Part II exam, most circuit calculations assume resistive loads unless a motor or transformer is explicitly identified. When motors appear, use Article 430 and remember that the power factor is already accounted for in the nameplate full-load current (FLC) tables.


1.2 Series Circuits

In a series circuit, components are connected end-to-end so that the same current flows through each element.

Rules:

Total resistance: R_total = R₁ + R₂ + R₃ + ...
Current is the same at every point: I_total = I₁ = I₂ = I₃
Voltage drops add to source voltage: V_source = V₁ + V₂ + V₃
Power adds: P_total = P₁ + P₂ + P₃

Practical method:

36.Find total resistance.
37.Find total current using Ohm's Law: I = V_source / R_total.
38.Find each voltage drop: V_n = I × R_n.
39.Check: sum of drops equals source voltage.

Field point: On a job site, a series circuit is rare in power distribution but common in control circuits (e.g., limit switches, safety interlocks). If a control circuit fails, measure voltage across each component to find the open device — the full source voltage will appear across the open element.


1.3 Parallel Circuits

In a parallel circuit, components are connected across the same two points, so each branch sees the full source voltage.

Rules:

Voltage is the same across each branch: V_source = V₁ = V₂ = V₃
Total current is the sum of branch currents: I_total = I₁ + I₂ + I₃
Reciprocal resistance formula: 1/R_total = 1/R₁ + 1/R₂ + 1/R₃
For two resistors only: R_total = (R₁ × R₂) / (R₁ + R₂)
Power adds: P_total = P₁ + P₂ + P₃

Practical method:

51.Find each branch current using Ohm's Law: I_n = V / R_n.
52.Sum branch currents to get total current.
53.If asked for total resistance, use R_total = V_source / I_total.

Exam trap: Many candidates incorrectly apply the two-resistor product-over-sum rule to three or more resistors. That rule works only for exactly two parallel resistors. For three or more, use the reciprocal method.

Field point: In a lighting circuit with multiple receptacles or luminaires, the loads are in parallel. When you add a branch, total current increases, and you must verify the conductor ampacity and overcurrent device rating per NEC 210.19 and 210.20.


1.4 Series-Parallel (Combination) Circuits

These circuits contain both series and parallel sections. The solution strategy is always the same:

59.Identify the parallel groups and reduce each to a single equivalent resistance.
60.Redraw the circuit as a simple series circuit.
61.Solve for total current using the source voltage and total equivalent resistance.
62.Work backwards to find voltage drops and branch currents in each original section.

Example approach:

If R₂ and R₃ are in parallel, and that group is in series with R₁:
R_parallel = (R₂ × R₃) / (R₂ + R₃)
R_total = R₁ + R_parallel
I_total = V_source / R_total
V₁ = I_total × R₁
V_parallel = I_total × R_parallel (this is also the voltage across both R₂ and R₃)
I₂ = V_parallel / R₂; I₃ = V_parallel / R₃

Exam trap: When you split the parallel voltage back into branch currents, do not use the total current for both branches. The sum of branch currents must equal the total current — use this as a check.


1.5 Voltage Drop — NEC 210.19(A)(1)

Voltage drop is a performance requirement, not a safety requirement. The NEC does not mandate a specific maximum voltage drop for branch circuits and feeders in most cases; however, 210.19(A)(1) Informational Note No. 4 recommends that conductors be sized so the voltage drop does not exceed 3% for a branch circuit or feeder, and 5% total from the service point to the farthest outlet.

Massachusetts note: 527 CMR 12.00 adopts the NEC with state amendments. For voltage drop, Massachusetts does not add a mandatory percentage beyond the NEC informational note, but the exam will expect you to know the 3%/5% figures and apply them when asked.

Voltage drop formula (single-phase):

VD = 2 × K × I × L / CM

Where:

VD = voltage drop in volts
K = resistance of conductor in ohm-circular mils per foot (approximately 12.9 for copper, 21.2 for aluminum at 75 °C)
I = load current in amperes
L = one-way length of conductor in feet
CM = circular mil area of the conductor (from NEC Chapter 9, Table 8)

Alternative formula (using ohms per 1000 ft):

VD = 2 × L × I × R / 1000

Where R is the conductor resistance in ohms per 1000 ft from NEC Chapter 9, Table 8.

Three-phase formula:

VD = 1.732 × K × I × L / CM

The factor 1.732 (√3) replaces the 2 because the current returns through a different phase conductor, reducing the effective loop length.

Percent voltage drop:

%VD = (VD / V_source) × 100

Practical method for sizing:

93.Determine the load current (I).
94.Measure or estimate the one-way conductor length (L).
95.Select a trial conductor size and look up its CM or resistance.
96.Calculate VD.
97.If %VD > 3% (branch) or > 5% (total), increase conductor size and recalculate.

Exam trap: Always use the one-way length in feet, not the round-trip. The formula already includes the factor of 2 for the return path. Doubling the length again is a common error.

Field point: On site, voltage drop matters for long runs to subpanels, parking lot lighting, and equipment pads. A journeyman should measure actual conductor lengths — do not trust the tape measure from the panel to the device; include vertical rises, horizontal runs, and slack at both ends.


1.6 Conductor Ampacity vs. Load Calculation

Do not confuse ampacity (the current-carrying capacity of a conductor under specific conditions) with load calculation (the sum of expected loads). The NEC separates these concepts:

Ampacity – Article 310, Tables 310.16 through 310.19 (2026 NEC reorganization). Adjustments for ambient temperature (Table 310.15(B)(1)) and bundling (Table 310.15(C)(1)) apply.
Branch circuit load – Article 220, Part III for dwelling units, Part IV for commercial.
Feeder load – Article 220, Part V.
Overcurrent protection – Article 240.

Minimum branch circuit conductor size is based on the load per 210.19(A)(1): the conductor must have an ampacity not less than the maximum load to be served. For continuous loads (3 hours or more), the load is calculated at 125% per 210.19(A)(1) and 210.20(A).

Exam trap: When a question says "continuous load," do not simply multiply the load by 1.25 for the conductor and then also multiply for the overcurrent device — you do both, but they are separate steps. The conductor ampacity must be ≥ 125% of continuous load; the overcurrent device rating must also be ≥ 125% of continuous load. If the conductor is already sized for the 125% factor, the breaker can match the conductor ampacity.


1.7 Motor Circuit Calculations (Article 430)

Motor calculations are a distinct subset because motors draw starting current well above running current, and the NEC provides specific rules.

Key sections:

430.6(A)(1) – For branch circuit conductors and overcurrent protection, use the table values from 430.247 through 430.250, not the motor nameplate. The nameplate is used only for overload protection (430.32).
430.22 – Branch circuit conductor ampacity must be at least 125% of the motor FLC from the tables.
430.52 – Branch circuit short-circuit and ground-fault protection (the "breaker") can be sized up to a percentage of FLC depending on the type of motor and protective device (e.g., 250% for inverse-time breakers on standard AC motors).
430.32 – Overload protection (the "heaters") is based on nameplate current, typically 115% to 125% depending on service factor and temperature rise.

Voltage drop for motors: When calculating voltage drop for a motor circuit, use the actual load current (which may be less than FLC) or the FLC from tables, depending on what the question asks. Do not use locked-rotor current (starting current) for voltage drop — that is a momentary condition.

Field point: A journeyman must read the motor nameplate for voltage, FLC, service factor, and temperature rise. The nameplate FLC is for overload sizing; the table FLC is for conductor and breaker sizing. Mixing these up is a classic exam failure.


1.8 Transformer Calculations

Transformers are covered under Article 450, but circuit calculations involving transformers require understanding the relationship between primary and secondary.

Basic relationships:

Voltage ratio: V_primary / V_secondary = N_primary / N_secondary
Current ratio (ideal): I_primary / I_secondary = V_secondary / V_primary
Power: VA_primary = VA_secondary (ignoring losses)

Sizing conductors for transformer secondaries:

450.3 – Overcurrent protection for transformers.
240.21(C) – Secondary conductor protection (tap rules).

Exam trap: For a single-phase transformer, the secondary full-load current is:

I_secondary = VA / V_secondary

For a three-phase transformer:

I_secondary = VA / (1.732 × V_secondary)

Field point: When connecting a step-down transformer, the primary current is lower than the secondary current. Many installers undersize the primary conductors because they look at the secondary load — always calculate both sides.


1.9 Power Factor and AC Circuits

For non-resistive loads (motors, fluorescent lighting ballasts, LED drivers), the power formula becomes:

P = V × I × pf

Where pf is the power factor (0 to 1).

Reactive loads:

Inductive loads (motors, ballasts) have a lagging power factor.
Capacitive loads (power factor correction capacitors) have a leading power factor.

Exam relevance: The Massachusetts exam rarely asks for power factor correction calculations, but you must understand that a motor's nameplate FLC already includes the effect of power factor. When using the NEC tables (430.247–430.250), the listed FLC values are based on typical motor power factors and efficiencies — you do not multiply by pf again.


1.10 Code Navigation — Where to Find It

Use this table to locate the governing rule during the open-book exam:

ConceptNEC Article / SectionMassachusetts / Other
Ohm's Law, power formulasNot in NEC — theory reference527 CMR 12.00 (adopts NEC)
Branch circuit conductor sizing210.19(A)(1)527 CMR 12.00
Voltage drop recommendation210.19(A)(1) Informational Note No. 4None (advisory)
Conductor ampacity tables310.16 – 310.19 (2026 NEC)527 CMR 12.00
Ambient temperature correction310.15(B)(1)
Bundling adjustment310.15(C)(1)
Load calculations (dwelling)Article 220, Part III
Load calculations (commercial)Article 220, Part IV
Feeder calculationsArticle 220, Part V
Overcurrent protectionArticle 240
Motor conductors430.22
Motor FLC tables430.247 – 430.250
Motor overloads430.32
Motor short-circuit protection430.52
Transformer overcurrent450.3
Secondary conductor taps240.21(C)
Conductor properties (CM, resistance)Chapter 9, Table 8
Box fill314.16
Conduit fillChapter 9, Tables 1–5
Fire alarm circuits (voltage drop)NFPA 72, Chapter 7 (notification appliances)527 CMR 12.00; MGL c.141

1.11 Common Exam Traps — Summary

149.Unit confusion: Convert all lengths to feet, all currents to amperes, all resistances to ohms before calculating.
150.Round-trip vs. one-way: Voltage drop formulas already include the 2 (single-phase) or 1.732 (three-phase) factor. Do not double the length.
151.Parallel resistor shortcut: The product-over-sum rule is for two resistors only.
152.Motor nameplate vs. table FLC: Use table FLC for conductors and breakers; use nameplate for overloads.
153.Continuous load factor: Apply 125% to both conductor ampacity and overcurrent device rating for continuous loads.
154.Three-phase power: When given a three-phase load in kVA, divide by (1.732 × V) to get line current, not by V alone.
155.Voltage drop percentage base: Use the nominal system voltage (120 V, 240 V, 480 V) as the denominator, not the actual measured voltage.
156.K factor: Use 12.9 for copper and 21.2 for aluminum unless the problem specifies a different conductor temperature or type.

1.12 Practical Field Points

Always verify voltage drop on long runs before pulling wire. It is far cheaper to upsize conductor on paper than to re-pull after installation.
Use a clamp meter to measure actual load current before sizing a replacement feeder. Nameplate ratings are maximums, not operating points.
When paralleling conductors (NEC 310.10), all conductors must be the same length, material, and cross-sectional area to ensure equal current division.
For motors, check the actual voltage at the motor terminals during starting and running. Low voltage causes high current and overheating.
Document your voltage drop calculations on the panel schedule or one-line diagram. Inspectors in Massachusetts may ask to see them for long branch circuits.

1.13 Summary

Circuit calculations on the Massachusetts Journeyman Part II exam are not about memorizing formulas — they are about applying the correct formula to the correct situation and navigating the NEC to verify sizing requirements. Master the distinction between ampacity, load, voltage drop, and overcurrent protection. Know where each rule lives in the 2026 NEC. And always check your units and your arithmetic before marking the answer.

The open-book format rewards candidates who know where to look as much as those who know how to calculate. Use the Code Navigation table above as your map, and practice each calculation type until the steps are automatic.

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free