Electrical Theory & Safety
JourneymanPractice study guide with diagrams.
Electrical Theory & Safety
Learning Objectives
Upon completing this chapter, you will be able to:
1.1 Fundamental Electrical Quantities
The electrician’s work is governed by four core quantities: voltage (E), current (I), resistance (R), and power (P).
Ohm’s Law states that voltage equals current times resistance: E = I × R. Rearranged: I = E ÷ R and R = E ÷ I.
Power Formula: P = E × I. Combining with Ohm’s Law gives P = I² × R and P = E² ÷ R.
Practical Field Point: When troubleshooting a circuit that trips a breaker, measure voltage first, then current. A high current reading with normal voltage indicates a short or overload; low voltage with normal current indicates high resistance (e.g., loose connection).
1.2 Series, Parallel, and Combination Circuits
Series Circuits
In a series circuit, components are connected end-to-end. The same current flows through all components. Total resistance is the sum: R_total = R1 + R2 + R3 + ... . Voltage drops across each resistor add up to the source voltage.
Key rule: If one component opens, the entire circuit stops working.
Parallel Circuits
In a parallel circuit, components are connected across the same two points. Voltage is the same across each branch. Total resistance is calculated as: 1/R_total = 1/R1 + 1/R2 + 1/R3 + ... . For two resistors, the shortcut is R_total = (R1 × R2) ÷ (R1 + R2) .
Key rule: Branch currents add up to the total current. If one branch opens, the others continue to operate.
Combination Circuits
These contain both series and parallel sections. Solve by reducing parallel groups to a single equivalent resistance, then add series resistances.
Common Exam Trap: Candidates often forget that in a parallel circuit, the total resistance is always less than the smallest branch resistance. If your calculation yields a value larger than the smallest resistor, you made an error.
NEC Connection: Article 210 addresses branch circuits. A multi-wire branch circuit (shared neutral) is a parallel application where the neutral carries only the unbalanced current. This is permitted under 210.4, provided all ungrounded conductors are disconnected simultaneously.
1.3 Alternating Current (AC) and Power Factor
Most commercial and industrial installations use AC. AC voltage alternates sinusoidally. Key values:
In AC circuits with inductive loads (motors, transformers), current lags voltage. With capacitive loads, current leads voltage. The phase angle (θ) between voltage and current determines the power factor (PF) : PF = cos θ.
NEC Connection: Article 220 requires load calculations to include the larger of the actual load or 125% of continuous loads. For motors, Article 430 requires the branch-circuit conductor ampacity to be 125% of the motor’s full-load current (FLC), which accounts for the motor’s starting current and thermal characteristics.
Practical Field Point: When measuring a motor circuit, use a clamp meter to compare the actual running current to the nameplate FLC. If the current exceeds the nameplate rating, the motor is overloaded or the voltage is low.
1.4 Grounding and Bonding
Grounding and bonding are critical for safety, ensuring that fault current has a low-impedance path to the source, which allows overcurrent devices to operate.
Key NEC Sections:
Critical Rule: The GEC is sized based on the largest ungrounded service conductor (Table 250.66), not on the load. The EGC is sized based on the overcurrent device rating (Table 250.122).
Common Exam Trap: Confusing the GEC and EGC sizing tables. The GEC uses Table 250.66; the EGC uses Table 250.122. They are not interchangeable.
Practical Field Point: When installing a subpanel, the neutral must be isolated from the enclosure (no bonding screw). The EGC and neutral are only bonded together at the first disconnecting means (service). This prevents parallel neutral paths and reduces shock hazards.
1.5 Overcurrent Protection
Overcurrent protection devices (fuses and circuit breakers) protect conductors and equipment from excessive current. The NEC defines three types:
Key NEC Sections:
Conductor Protection Rule (240.4): The overcurrent device rating must not exceed the conductor’s ampacity, except for the "next size up" rule. If the ampacity does not correspond to a standard rating, you may use the next higher standard rating, provided it does not exceed 800 A and the conductor is not part of a multi-outlet branch circuit supplying receptacles.
Common Exam Trap: The "next size up" rule applies only to standard overcurrent device ratings. You cannot round up arbitrarily; you must use the next standard size.
1.6 Voltage Drop
Voltage drop is the reduction in voltage along a conductor due to resistance. Excessive voltage drop causes poor equipment performance and overheating.
NEC Reference: The NEC does not mandate a specific voltage drop for general circuits, but 210.19(A) Informational Note and 215.2(A)(1) Informational Note recommend a maximum of 3% for branch circuits and 5% total (feeders + branch circuits).
Formula for single-phase:
VD = (2 × K × I × L) ÷ Cmils
Where:
For three-phase, multiply by 1.732 instead of 2: VD = (1.732 × K × I × L) ÷ Cmils.
Practical Field Point: For a 120 V circuit, 3% drop equals 3.6 V. For a 240 V circuit, 3% equals 7.2 V. Use these thresholds to decide if you need to upsize the conductor.
Common Exam Trap: The length (L) in the formula is the one-way distance, not the total round-trip. The factor of 2 (or 1.732) already accounts for the return path.
1.7 Electrical Safety: Lockout/Tagout and Arc Flash
Safety is the foundation of the trade. The NEC works in conjunction with OSHA standards (29 CFR 1910.147 for LOTO, 1910.269 for electric power).
Lockout/Tagout (LOTO) : Before working on any circuit, you must:
Arc Flash: An arc flash is a dangerous release of energy caused by an electric arc. The NEC requires equipment to be marked with warning labels (Article 110.16) indicating the arc-flash hazard.
Approach Boundaries (per NFPA 70E, not NEC, but essential knowledge):
PPE Categories range from 1 (low risk) to 4 (high risk). Category 4 requires an arc-rated suit with a minimum rating of 40 cal/cm².
Practical Field Point: Always verify the absence of voltage at the point of work, not just at the panel. Use a voltage tester that you have tested on a known live source immediately before and after checking the de-energized circuit.
1.8 Code Navigation: Where to Find Key Concepts
| Concept | NEC Location |
|---|---|
| Definitions (grounded, bonding, etc.) | Article 100 |
| Branch circuits | Article 210 |
| Feeders | Article 215 |
| Overcurrent protection | Article 240 |
| Grounding and bonding | Article 250 |
| Wiring methods | Articles 300–398 |
| Conductors for general wiring | Article 310 |
| Motors | Article 430 |
| Transformers | Article 450 |
| Services | Article 230 |
| Load calculations | Article 220 |
| Conductor properties (cmils, resistance) | Chapter 9, Table 8 |
| Ampacity tables | Table 310.16 (copper/aluminum) |
| EGC sizing | Table 250.122 |
| GEC sizing | Table 250.66 |
| Standard overcurrent ratings | 240.6(A) |
| Arc-flash labeling | 110.16 |
| Voltage drop (informational) | 210.19(A) Note, 215.2(A)(1) Note |
Exam Strategy: In the open-book exam, do not memorize tables. Instead, memorize the article numbers and table numbers. When you see a question about "sizing an equipment grounding conductor," your first action is to flip to Table 250.122, not to search the index.
1.9 Common Exam Traps and How to Avoid Them
Summary
This chapter covered the essential theory and safety concepts that underpin the Texas Journeyman exam. Master the calculations for Ohm’s Law, power, and voltage drop. Understand the difference between grounding and bonding, and know exactly where to find the sizing tables in the NEC. Finally, always prioritize safety: LOTO procedures, arc-flash awareness, and verifying a zero-energy state are non-negotiable habits for a professional journeyman.
This chapter is for study purposes only and does not replace the official NEC text. Always consult the current edition of NFPA 70 for code requirements.
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free